DC48V 200A 10700W Telecom Rectifier System, Input Voltage: 220VAC,
Output Voltage: 48VDC
Quick Details:
Place of Origin: Shenzhen, China (Mainland) | Input Voltage: AC220V |
Brand Name: ESTEL | Output Voltage: DC48V |
Model Number: GPE48200E | Output Power:10700W/5350W |
Product Name: Telecom Power System | Input Frequency: 45~65Hz |
Certification: ISO9001, CE, 3C, FCC, TLC | Max. Input Current: 67A |
Installation Mode: 19” cabinet installed | Power Factor: 0.98 |
Application: outdoor telecom base station | Components: 4×50A rectifier module, 1×monitoring module, 1×PDU |
Payment & Shipping Terms:
Minimum Order Quantity: | 1 set |
Price: | negotiation |
Payment Terms: | L/C, D/A, D/P, , T/T, Western Union |
Supply Ability: | 20,000 sets per month |
Delivery Time: | 7-10 working days |
Packaging Details: | carton/wooden case |
1. Application
(1) Small scale program controlled exchangers
(2) Access network
(3) Transmission equipment
(4) Mobile communication
(5) Satellite communication ground station
(6) Microwave communication
2. Features
(1) Adoption of active power factor compensation technology with factor >0.98
(2) Wide operating range of AC input voltage: 90~290Vac
(3) Operating temperature range: -25°C~+55°C
(4) Zero current/voltage switching tech with high efficiency ≥91%
(5) Lifecycle of battery prolonged by perfect battery management, including electrical charge/discharge management, battery temperature compensation, battery capacity test, reversal connection proof protection, low voltage protection etc.
(6) Hot-swappable
(7) Input over/under voltage protection
(8) Output over voltage protection
(9) Output over current protection
(10) Output short circuit protection
(11) Auto current sharing, parallel output
(12) Embedded mounting
The system consists of power distribution unit, rectifier module (from 1 set, up to 4 sets) and 1 monitoring module. The configuration is optional, as following table:
Configuration | Rectifier Module | Monitoring Module | Power Distribution |
Standard | GPR4850D-R01 | AC power distribution: single-phase input, AC breaker @ general line (80A/2P) ; DC power distribution: battery MCB 100A/1P×2; LVLD: 32A×2, 63×2, 16×6 (MCB capacity optional) LVBD: 16A×2, 10A×2 (MCB capacity optional) |
AC power is first input AC-INPUT MCB and then feed into the rectifier module after lightning proof and filtering. AC-INPUT acts as protection to over load and short circuit to AC power. The user’s battery is connected to the DC output side through MCB BAT and KM2, and the circuit breaker provides disconnection control, over-load and short-circuit protection to the battery.
Under normal conditions, every parameter of rectifier modules and power distribution unit are all under control of the monitoring module, operating according to the pre-set parameter or user’s commands. If AC mains faults, the battery will power to the system. With the battery discharge, the terminal voltage of the battery starts to descend. When battery voltage is under -47V±0.5V, the monitoring module sends DC under voltage alarm signal and when battery voltage is under -46.0V±0.5V (adjustable), the KM1cuts off non-priority loads and retaining power to priority loads. If battery voltage drops to -43.0V±0.5V (adjustable), the KM2 will cut off output of priority loads and then the power system will stop working. If the external AC mains recovers, the system will normally work again. (All above monitoring data are system default values and can be reset by user).
Except for battery over-discharge protection, battery or load
over-temperature protection is prohibitive under default, users can
send command to activate or inactivate according to the demanding.
Environment | |||||
Item | Min. | Typical | Max. | Unit | Remark |
Operating temperature | -25 | 55 | °C | When ≥55°C, decreased power output | |
Storage temperature | -40 | 80 | °C | ||
Humidity | 10 | 90 | % | Relative humidity without condensing | |
Atmospheric pressure | 70 | 106 | KPa | ||
Altitude | 0 | 3000 | m | ||
Cooling | Forced cooling with fan |
Input | |||||
Item | Min. | Typical | Max. | Unit | Remark |
Input voltage range | 90 | 220 | 290 | Vac | |
Input frequency | 45 | 50 | 65 | Hz | |
Max. Input current | 67 | A | |||
Power factor | 0.98 | Rated load | |||
Input over voltage protection point | 300 | Vac | Automatically recoverable | ||
Input over voltage recovery point | 290 | Vac | Return difference ≥5V | ||
Input under voltage protection point | 85 | Vac | Automatically recoverable | ||
Input under voltage recovery point | 90 | Vac | Return difference ≥5V | ||
Input over current protection | MCB in AC Input supply protection |
Output (Table 1) | |||||
Item | Min. | Typical | Max. | Unit | Remark |
Output voltage | 42 | 53.5 | 58 | Vdc | Adjustable by monitor, tested in no load |
Output power | 10700 | W | 10700W output when input voltage is 176~290VAC (rated power includes battery charging power plus load power) | ||
5350 | W | 90~175VAC input | |||
Output over voltage protection point | 58.5 | 60.5 | Vdc | Lock up | |
Output current limiting protection point | Output current limiting protection | ||||
Output short circuit protection | Long-term short circuit protection, automatically recoverable | ||||
Over temperature protection | Automatically recoverable in ambient temperature lower than 65°C | ||||
Battery power-down protection | Battery power-down protection | ||||
Battery polarities reversal connection protection | No damage on battery and power system | ||||
Voltage regulation accuracy | ±1 | % |
Output (Table 2) | |||||
Item | Min. | Typical | Max. | Unit | Remark |
Temperature coefficient | ±0.2 | ‰/℃ | |||
Current sharing unbalance | ±5 | % | Within 50~100% load range | ||
Start-up/shut-down overshoot range | ±5 | % | Any module is removed when operating, (the load current should be less than total output current of working rectifier modules), the system output voltage fluctuates | ||
Dynamic response recovery time | 200 | uS | 25%~50%~25% load variation 50%~75%~50% load variation | ||
Dynamic response overshoot | ±5 | % | Rated output voltage, rated load current | ||
Efficiency | ≥91 | 92 | % | 220Vac input, rated output voltage, rated load current | |
83 | % | 110Vac input, rated output voltage, rated load current | |||
Start-up time | 3 | 8 | S | pre-current limiting is fitted with start-up output between rated start up input voltage and rated output voltage established period | |
Pressure drop | 500 | mV | |||
Peak-peak noise voltage | 200 | mV | |||
Psophometrically weighted noise voltage | 2 | mV |
Other Parameters | |
Item | Requirement |
Acoustic noise | ≤55dB(A) |
Smelling | any abnormal and poisonous smelling is not allowed |
Components | rated temperature of the electrolytic capacitor ≥105℃ |
Hot swappable | the rectifier module meets the hot-swappable requirement |
Mixed insertion | rectifier modules can be mixed insertion |
Ineffective separation | rectifier module can separate with system when it is ineffective |
Cooling | forced cooling by fan mounted on rectifier, face in, back out. The fan is mounted on rectifier front panel; can be disassembled. Fans include temperature control speed adjusting function. |
Insulation Rating | |||||
Parameters | Min. | Typical | Max. | Unit | Remark |
Input-chassis | 3535 | Vdc | |||
Input-output | 3535 | Vdc | |||
Output-chassis | 1414 | Vdc | |||
Insulating Resistance | In normal atmospheric pressure, when relative humidity is 90%, testing voltage is 500VDC, the insulating resistance of input-output, input-grounding, output-grounding are all ≥10MΩ |
Mechanical specifications | |
Dimensions (Overall) | as the following diagram |
Weight(kg)(Overall) | ≤23.5kg (Inclusive of module) ≤13.5kg (Frame + Distribution, exclusive of module) |
Chassis connects with external electric through system interface board. As shown in figure below:
Descriptions:
1. Signal transfer board;
2. BAT- ;
3. LVBD ;
4. LVLD ;
5. AC Input ;
6. Anode Copper Bar;
7. Ground Copper Bar;
7. Packing and Shipping
Our Delivery Agent
The goods can be shipped by sea, by air, by courier, by land, by
train, etc.
Besides the following delivery agent, we can also look for the
delivery agent with the best price in china if you need us to do
for you.
8. Our Contact Information
Mobile Phone: 0086-13752765943
Telephone: 0086-0755 66600941
Email: info@estel.com.cn
lxf.estel@hotmail.com
Skype: fiona.liang10
9. Our Partner
Tianjin Estel Electronic Science and Technology Co.,Ltd
Introduction
Tianjin Estel Electronic Science and Technology Co., Ltd (ESTEL(GUANGDONG)TECHNOLOGY CO., LTD), located in China, is a professional supplier of integrated outdoor telecom cabinet and temperature control solutions for outdoor telecom base station. As a science and technology innovative company, we engage in the R&D, manufacture, and sales of telecommunication equipment. Estel has a well-established team of technical and management experts who can meet customers’ specific needs accurately.
The base station integrated solutions and products include outdoor integrated telecom equipment cabinet, battery cabinet, RRU cabinet, power supply cabinet, environment monitoring system, TEC peltier air conditioner, AC220V compressor air conditioner, DC48V variable frequency air conditioner, heat exchanger, rectifier, UPS, embedded telecom power system etc. All the above solutions and products can be custom made.
Our products and solutions have been deployed all over China. Our main domestic customers are China Telecom, China Mobile, China Unicom, State Grid, Shenzhen / Beijing Metro and Huawei / ZTE etc. In addition, our products have been exported to Europe, North America, South America, Central America, Southeast Asia, Africa, Australia, Mid East countries, etc.
“ Customers First, Quality First ” is always our principle. We have attained many certifications, such as ISO9001, ISO14001, OHSAS18001, CE, UL, FCC etc. AS a telecom integrated solutions / energy saving system integrator in China, We have strong advantages in technology competitiveness, management competitiveness ,service competitiveness and price competitiveness. Through many years of experiences in design, production and implementation of different projects around the world, we have gained great reputation. Relying on professional technique and strict quality control, we will continuously offer high cost-effective products and solutions to our respectable customers globally. We will always try our best to meet customers’ need and requirement.
Company Capability
Trade & Market
Main Markets | Total Revenue (%) |
Domestic Market | 50.00% |
Africa | 15.00% |
Southeast Asia | 10.00% |
South America | 5.00% |
Central America | 5.00% |
Australia | 3.00% |
Mid East | 3.00% |
North America | 2.00% |
Southern Europe | 2.00% |
Eastern Europe | 1.50% |
Northern Europe | 1.00% |
Western Europe | 1.00% |
South Asia | 1.00% |
Eastern Asia | 0.50% |